PHOTOELECTRIC SMOKE/HEAT DETECTOR WITH BUILT-IN WIRELESS TRANSMITTER

Category:

Description

FEATURES

• Improved Robust RF Field
Strength
The distance between the detector
and receiver has been significantly
increased without the need for a
repeater
• Smoothing Algorithms
Mathematical calculations in the
detector’s software that minimize
nuisance alarms by smoothing out
short term spikes from dust and
smoke
• Smart Check
A signal is sent to the control panel
when the detector requires cleaning.
This allows a regular, non-emergency
service call to clean the detector
before it goes into alarm.
• Drift Compensation
Virtually eliminates nuisance alarms
from long-term dust build-up by
automatically adjusting the detector’s
sensitivity
• Removable Detector Cover and
Chamber Top
The technician is able to quickly and
easily clean the detector chamber
without disassembling the detector
head
• Approved UL Listings for Residential
and Commercial Applications
Both residential and commercial
installation requirements are met
• Additional LED Status Indicators
Identifying between alarm or trouble
conditions is a snap with green and
red LED status indicators. A green LED
denotes a normal condition while the
red LED indicates abnormal conditions.
• Easy-to-install Mounting Base
The sturdy mounting base allows the
detector to be more easily installed
on uneven surfaces (i.e. stucco). The
mounting base has larger mounting
ports, which accommodate drywall
anchors for easy surface mounting.
ADDITIONAL FEATURES:
• Utilizes one long-life 3V lithium
battery
• Microcontroller runs on a 4.0 MHz
clock
• Horn operates at 3.3 KHz with sound
pressure level of 85 dBA at 10 feet
• Built-in wireless transmitter, temporal
code 3 sounder
• Maintenance signal fully complies
with the sensitivity test requirement
specified in NFPA 72, 7-2.2 and is
approved by UL